Magvatech SGF/MVT

SF6-Free Switchgear

Medium voltage switchgear with no SF6 gas anywhere in the panel, so there is nothing to monitor for leaks and nothing to recover at end of life. Air-insulated, maintenance free, with embedded fast arc protection.

The SGF/MVT range is air-insulated switchgear that contains no SF6 gas at all. For a utility or plant operator that removes a whole category of obligation: no gas pressure monitoring, no leak reporting, no handling procedure, and no end-of-life gas recovery.

SF6 has a global warming potential roughly 23 000 times that of CO2, and its use in new electrical equipment is being restricted in a growing number of markets. Choosing an SF6-free panel now avoids a retrofit decision later.

Magvatech describe the SGF/MVT as the most compact and endurant SF6-free switchgear in the world. It is maintenance free, has embedded fast arc protection, and remote control is available.

Magvatech SGF/MVT SF6-free switchgear, a four-panel medium-voltage lineup with a protection relay on each cubicle

Ratings

SGF/MVT switchgear ratings
ParameterSGF_1SGF_2
Rated maximum voltage (Ur)17.5 kV17.5 kV
Power frequency withstand (Ud), 1 min38 kV38 kV
Lightning impulse withstand (Up)95 kV95 kV
Rated continuous current (Ir)800 A1250 A
Short-circuit breaking current (Isc)25 kA31.5 kA
Short-time withstand current (Ik)25 kA31.5 kA
Duration of short circuit (tk)1 s1 s
Mechanical endurance50 000 CO30 000 CO
Electrical endurance at rated load50 000 CO30 000 CO
Endurance at rated breaking current100 CO25 CO
Closing time< 41 ms< 31 ms
Opening time< 22 ms< 22 ms
Opening from arc protection< 60 ms< 60 ms
Internal arc classificationAFL 25 kA, 0.2 sAFL 31.5 kA, 0.2 s
Net weight240 kg310 kg

Ratings from the Magvatech SGF/MVT technical booklet (EN 3.2). Both panels are rated 50/60 Hz, IP4X, operate from −45°C to +40°C at up to 95% humidity, and use a monostable magnetic actuator with an 85 to 265 V AC/DC supply. Disconnector switch endurance is 2000 earthed-isolated-engaged cycles.

Why SF6-free matters here

  • No gas handling obligations

    Nothing to monitor for leaks, top up, or recover and dispose of at end of life.

  • Maintenance free

    No scheduled gas or mechanism maintenance across the panel's service life.

  • Embedded arc protection

    Fast arc protection is built in, opening in under 60 ms when triggered.

  • Compact footprint

    Designed to fit substation buildings and plant rooms where space is constrained.

  • Long switching life

    Up to 50 000 CO operations at full load on the SGF_1 panel.

  • Remote control available

    Suits distribution automation schemes and remote substation operation.

Installed and commissioned by us

We install and commission SGF/MVT lineups on site, including protection relay configuration, functional testing and network integration. The photographs on our homepage and about page are our own installations.

Installation services
SGF/MVT switchgear bays installed at a client site by AM Power Solutions

Planning a switchgear installation?

Tell us what you need and we will come back to you with a clear quote.