VTOP series

Voltage Transformers

Outdoor voltage transformers for metering and protection on 11kV, 22kV and 33kV networks, commonly supplied alongside recloser installations.

A voltage transformer steps network voltage down to a standard secondary level so metering and protection equipment can measure it safely. On a recloser installation it does two jobs at once: it gives the controller its voltage reference, and it supplies the control cabinet itself.

The VTOP series is built for outdoor pole and structure mounting on 11kV, 22kV and 33kV networks. The cast resin body is rated for heavy pollution, which is what coastal and industrial lines in South Africa actually need.

Specifications are confirmed per order. Burden, accuracy class and voltage factor all depend on what the secondary is feeding, so tell us the application and we will confirm the unit.

Ratings

Outdoor voltage transformers for metering and protection on 11kV, 22kV and 33kV networks.

VTOP series voltage transformer ratings
ParameterVTOP-2-15VTOP-2-25VTOP-2-36
Network11 kV22 kV33 kV
Rated transformer ratio11000 / 220 V22000 / 110 V33000 / 110 V
Maximum operating voltage15 kV25 kV36 kV
Lightning impulse withstand95 kV125 kV170 kV
Power frequency withstand, 1 min35 kV50 kV70 kV
Accuracy class333
Rated burden200 VA200 VA200 VA
Maximum power600 VA400 VA800 VA
Voltage factor1.9 Un1.2 Un1.2 Un
Rated frequency50 (60) Hz50 (60) Hz50 (60) Hz

Figures taken from factory routine test reports issued under IEC 61869-1 and IEC 61869-3. Ratings are confirmed per unit at time of order, so please confirm the specification for your application before ordering.

Where they are used

  • Recloser installations

    Commonly supplied alongside an auto recloser to provide the control supply and the voltage measurement reference.

  • Metering

    Stepping network voltage down to a standard 110 V or 220 V secondary for metering equipment.

  • Protection schemes

    Providing the voltage input for protection relays and network monitoring.

  • Outdoor mounting

    Built for outdoor pole or structure mounting, not for indoor panel installation.

  • Tested to IEC 61869

    Manufactured and routine tested against IEC 61869-1 and IEC 61869-3.

  • Supplied with test certificates

    Each unit ships with its factory routine test report covering ratio, accuracy class and withstand testing.

Ordering

Voltage transformer specifications are confirmed per order, including burden, accuracy class and voltage factor. Tell us the network voltage, what the secondary needs to feed, and whether the unit is for metering, protection or both, and we will confirm the right specification and availability.

Need voltage transformers?

Tell us what you need and we will come back to you with a clear quote.